LVM-3P

Protection of 3 Phase devices against Over voltage, Under voltage unbalance supply is one of the major issue in electrical systems. For safe running of 3-phase devices, special protections that keep a continous watch on supply conditions are very essentials. The major cause of maximum load burn-out is overloading which occurs due to unbalance supply. Single phasing & Reverse phasing conditions LVM-3p detects such conditions & protect the load from burn cut.

'PROTONs LVM-3P' offer following protections with precise accuracy. LOW/HIGH voltage tripped to ensure trouble free running of 3-phase Loads. Reverse phasing or imbalance in Phase voltages, Single phasing protection.

Salient Features :-

  • Microcontroller based system.
  • Suitable for Tree phase load.
  • Protection against over voltage
  • Protection against Under voltage.
  • Protection against Single phasing & unbalance.
  • Protection against Reverse phasing.
  • Trip indication for Faults, indication for output relay ON.
  • Under voltage/Over voltage set points are setable.
  • No seperate auxiliary supply required.

Technical Specifications :-

Supply voltage: 3 Phase 415VAC, 50Hz(No auxilliary supply)
Output Contacts : Twochangeover(NC-C-NO),Rating 5A at 230VAC
Voltage trip setting : Over voltage limit can be set within 430 to 470VAC Hysterisis between cut off & cut in 10V
Under voltage limit can be set within 330 to 370VAC Hysterisis between cut off & cut in 10V
Trip Time delay 50msec
Reset Mode Healthy (ON) : Green LED
Indications Healthy (ON) : Green LED
Over Voltage (OV) : Red LED
Under Voltage (UV) : Red LED
Single Phase (SPP) : Red LED
Reverse Phase (REV PHASE): Red LED
Operating Temperature Range -5 0C to 60 0C
Relative Humidity Din Rail: Base mounting
Mounting dimentions.: 62 (W) X 70 (L) X 110 (D) mm

Working :-

In the normal run mode, if the supply is within the range then Relay will be ON. If Over voltage, Under voltage, SPP, Unbalance & Reverse phasing returns in the supply then Relay will be Off & corresponding Fault LED start blinking.

OV : It becomes blinking when, voltage increases above set limit.
UV : It becomes blinking when, voltage decreases below set limit.

SPP: It becomes blinking when, B phase is abset or phase to phase Unbalance. (UB: 65+/-10V)
REV PHASE: It becomes blinking when, phase Sequence is changees, Hystesis between at off & cut in is 10V.

SETTING: OV : Over voltage limit can be set with in 430VAC to 470VAC by OV preset.

UV : Under voltage limit can be set with in 330VAC to 370VAC by UV preset.